autocast universal
®
230 Casting System Error signals – causes and remedies Stand 1.9. 03 B 29
Error signals –
causes and remedies
If an error occurs during operation or during the
process, it is displayed on the touch panel and a buzzer
is heard at intervals of one sec. When the error has
been corrected, the signal must be acknowledged by
touching Quit.
¡
The following problems may occur:
Signal Cause Effect Remedy
Check door / lift Started with door open Process start Flip toggle
Started with casting mould not prevented. switch to upper
clamped (toggle switch not No value in position, close door
up) service mode
No quantity selected Started without selecting melt Process start Select melt quantity
quantity (fig. 2) prevented.
No value in service
mode
No arc current Plasma source does not generate Process aborted. Place material in
current despite inverter being No value in service crucible
switched on mode Check electrode
●
No material in crucible Inverter check
●
Defective electrode only by approved
●
Defective inverter electrician!
Chamber Temperature in casting chamber No effect on current Switch unit off and
temperature too high process, new process allow to cool
start prevented
Ring defective, Pressure increase in casting . Pressure monitoring Replace ring.
STOP! chamber during melting process system detects Check seal.
due to defective ring continuous excessive
pressure (min. 3 sec.)
in melting chamber.
Melting process
aborted. Cool off.
No tilting of crucible.
No value in service
mode.